How often is PAT testing needed?

There's no fixed legal interval. Here's how to set a sensible one for your premises, and save money doing it.

PAT testing
Updated 20 October 2026
6 min read

"Every 12 months" is a myth. The right interval depends on the equipment, how it's used and where. Here's a practical way to decide.

What the law actually says

The Electricity at Work Regulations 1989 require electrical equipment that could cause danger to be maintained so it doesn't. The Provision and Use of Work Equipment Regulations 1998 say much the same for work equipment generally. Neither sets a testing interval, and neither uses the term "PAT testing". HSE's position is that the frequency of inspection and testing should be based on risk.

So the legal question isn't "have you tested every 12 months?" but "have you done enough to keep the equipment safe, and can you show it?"

The three levels of checks

  1. User checks: anyone using equipment glancing at the plug, flex and casing before use. They cost nothing and find a lot.
  2. Formal visual inspection: a trained person removing the plug cover, checking the fuse and cord grip, and recording it. Most faults are found here.
  3. Combined inspection and testing: the electrical tests (earth continuity, insulation, polarity) that find faults you can't see.

Good maintenance means using all three, with testing less often than inspection.

Suggested starting intervals

Environment / equipmentFormal visual inspectionCombined inspection and test
Office IT, monitors, desk equipment1–2 yearsEvery 2–4 years, or not at all for some Class II items
Office kettles, heaters, extension leads6–12 months1–2 years
Shops and hospitality front of house6–12 months1–2 years
Commercial kitchens3–6 months6–12 months
Salons and barbers (hand-held)3–6 months6–12 months
Rented homes (supplied appliances)Each change of tenancyEach change of tenancy, or yearly in HMOs
Schools (classroom equipment)Yearly1–4 years depending on use
Construction sites, 110 V toolsWeekly user checksEvery 3 months
Hire equipmentBefore each hireBefore each hire, or on a short cycle

These are starting points based on the IET Code of Practice approach and HSE guidance. Adjust them using your results: if nothing fails over two cycles, you can usually extend; if a lot fails, shorten.

Things that need more frequent checks

  • Equipment that is moved around, plugged and unplugged a lot;
  • Hand-held equipment, especially with heating elements;
  • Anything used outdoors, in wet areas or in kitchens;
  • Extension leads and multi-way adaptors;
  • Equipment used by the public or by people unlikely to report damage.

Keeping records

The law doesn't require a register, but it's the easiest way to show you're managing the risk, and insurers, licensing officers and event organisers often ask for one. A good register lists each item, its location, its class, the result and the next due date. Ours does exactly that. See our PAT testing service.

Questions people ask

Is yearly PAT testing a legal requirement?

Do Class II (double insulated) items need testing?

Do landlords need PAT testing every year?